Kermi Heat pump ​

Integrates the X-Center Device (X-Center Pro) of Kermi Heat pump. Kermi X-Center & other attached devices (in progress) are integrated into the Modbus Binding.

This binding was tested and developed with Kermi x-change dynamic pro heat pump (build 2023).

Hint: This binding may also work with devices from "Bösch" in Austria, which is a sub-brand of Kermi, they are nearly identically.

Prerequisite ​

Requirement is contacting Kermi Support to activate Modbus-TCP which can be connected directly by network. Older devices (non-Pro ?) were connected by Modbus-RCP - maybe you can try to connect them here using a Modbus-TCP modulator (e.x. from waveshare or similar).

Supported Things ​

First you need a "Modbus TCP-Bridge" which establishes the basic connection towards your X-Center device.

NameThing Type IDDescription
Kermi Heat Pump X-Centerkermi-xcenterProvides (electric) Power values, Flow-information, PV-States, Temperatures and general Information of your Kermi Heat Pump

Discovery ​

This binding does not support autodiscovery.

Device IDs ​

DeviceDevice IDComment
X-Center40on cascade-circuits: slave1: 41, slave2: 42, ...

Thing Configuration ​

The needed Bridge can be found in the Modbus Binding and have to be added manually without Discovery.

  1. Create Modbus TCP Slave (Bridge) with matching Settings of your Kermi Device:
  • IP Address - IP Address or hostname of your heatpump
  • Port - Port of modbus on your heatpump (normally 502)
  • Device ID - ID on modbus, 40 is default for Kermi (see Device IDs)
  1. Create Kermi Heat Pump X-Center and attach it to the previous installed Modbus TCP Slave (Bridge). Configuration requires an appropriate Data Refresh Interval with more than 2000 Milliseconds, default is 5000. If it's too fast, you may experience errors in openHAB or your X-Center! Reboot if X-Center stops responding on network access. You can enable "PV Modulation" if you want to read the values (default: disabled)

Details on Configurations explained below.

Modbus TCP Slave ​

ParameterTypeDescription
hosttextIP Address or reachable hostname of your device
portintegerTCP Port of your Kermi device Modbus Settings. Default is 502
deviceIdintegerModbus ID of your Kermi device Modbus Settings. Default is 40

Kermi Heat Pump X-Center ​

Select as Bridge your previously created Modbus TCP Slave.

ParameterTypeDescription
refreshintegerRefresh Rate of X-Center values in Milliseconds (default:5000)
pvEnabledbooleanRead PV-Modulation (default:false)

Kermi StorageSystemModule (support planned in future releases) ​

Select as Bridge a separate (second) Modbus TCP Slave.

ParameterTypeDescription
hosttextIP Address or reachable hostname of your device (same as X-Center)
portintegerTCP Port of your Kermi device Modbus Settings. Default is 502
deviceIdintegerModbus ID of your Kermi device Modbus Settings. Default is 50

Channel-Groups ​

The X-Center / StorageSystemModule device offers quite an amount of channels. They are grouped into 7 channel-groups:

  • State
  • EnergySource
  • Charging Circuit
  • Power & Efficiency
  • Workhours
  • Alarm
  • PV Modulation

Channels ​

Status ​

Channel IdChannelTypeDescription
global-state-idGlobal State IDNumberState of heat pump as Number, displayed as readable State-Text in UI

Possible states:

  • Standby
  • Alarm
  • DrinkingWater
  • Heating
  • Defrost
  • Preparing
  • Blocked
  • EVU Blocktime
  • Unavailable

Energy-Source ​

Channel IdChannel LabelChannnel IdTypeDescription
exit-temperatureExit temperatureNumber<Temperature>in °C - Air temperature exiting heat pump
incoming-temperatureIncoming temperatureNumber<Temperature>in °C - Air temperature incoming into heat pump
temperature-sensor-outsideTemperature OutsideNumber<Temperature>in °C - Outside Air Temperature (if connected)

Charging Circuit ​

Channel IdChannel LabelTypeDescription
flow-temperatureFlow temperatureNumber<Temperature>in °C - Water temperature from heat pump to drinking water or heating circuit
return-temperatureReturn temperatureNumber<Temperature>in °C - Water temperature returning back to heat pump
flow-speedFlow speedNumber<VolumetricFlowRate>in l/min - Flow speed of the water

Power and efficiency ​

Channel IdChannel LabelTypeDescription
copCurrent COPNumbercurrent cop overall (Coefficient Of Performance)
cop-heatingCurrent COP heatingNumbercop for heating
cop-drinkingwaterCurrent COP drinking waterNumbercop for drinking water
cop-coolingCurrent COP coolingNumbercop for cooling
powerCurrent powerNumber<Power>in W (Watt) - Power overall
power-heatingCurrent power heatingNumber<Power>in W (Watt) - Power for heating
power-drinkingwaterCurrent power drinking waterNumber<Power>in W (Watt) - Power for drinking water
power-coolingCurrent power coolingNumber<Power>in W (Watt) - Power for cooling
electrical-powerCurrent electric powerNumber<Power>in W (Watt) - electric Power overall
electrical-power-heatingCurrent electric power heatingNumber<Power>in W (Watt) - electric Power for heating
electrical-power-drinkingwaterCurrent electric power drinking waterNumber<Power>in W (Watt) - electric Power for drinking water
electrical-power-coolingCurrent electric power coolingNumber<Power>in W (Watt) - electric Power for cooling

Workhours ​

Channel IdChannel LabelTypeDescription
workhours-fanFan workhoursNumber<Time>in h (hour) - worked hours of the fan
workhours-storage-loading-pumpStorage Loading Pump workhoursNumber<Time>in h (hour) - worked hours of the storage loading pump
workhours-compressorCompressor workhoursNumber<Time>in h (hour) - worked hours of the compressor

Alarm ​

Channel IdChannel LabelTypeDescription
alarm-stateAlarm stateSwitchOn / true if an alarm is raised

PV Modulation ​

Channel IdChannel LabelTypeDescription
pv-statePV Modulation ActiveSwitchOn / true if PV Modulation is currently active
pv-powerPV PowerNumbery<Power>in W (Watt) - Power of PV Modulation
pv-target-temperature-heatingTarget temperature heatingNumber<Temperature>in °C - target Temperature in PV Mode of heating (storage)
pv-target-temperature-drinkingwaterTarget temperature drinking waterNumber<Temperature>in °C - target Temperature in PV Mode of drinking water (storage)

Full Example ​

Attention: Configuration by file is not recommended. You can configure everything in the main UI.

kermi.things Example ​

dsl
Bridge modbus:tcp:device "Kermi X-Center Modbus TCP" [ host="xcenter", port=502, id=40 ] {
  Bridge kermi-xcenter heatpump "Kermi X-Center Heat Pump" [ refresh=5000, pvEnabled=false ]
}

Items ​

dsl
Number    XCenter_Global_State_Id                 "X-Center Global State ID"            (kermi)      { channel="modbus:tcp:device:heatpump:state#global-state-id" }

Number:Temperature        Heatpump_FlowTemperature       "Flow Temperature" (kermi,persist) { channel="modbus:tcp:device:heatpump:charging-circuit#flow-temperature" }
Number:Temperature        Heatpump_ReturnTemperature     "Return Temperature" (kermi,persist) { channel="modbus:tcp:device:heatpump:charging-circuit#return-temperature" }
Number:VolumetricFlowRate Heatpump_FlowSpeed             "Flow Speed" (kermi,persist) { channel="modbus:tcp:device:heatpump:charging-circuit#flow-speed" }

Number:Temperature        Heatpump_ExitTemperature       "Exit Temperature" (kermi,persist) { channel="modbus:tcp:device:heatpump:energy-source#exit-temperature" }
Number:Temperature        Heatpump_Incomingtemperature   "Incoming temperature" (kermi,persist) { channel="modbus:tcp:device:heatpump:energy-source#incoming-temperature" }
Number:Temperature        Heatpump_TemperatureOutside    "Temperature Outside" (kermi,persist) { channel="modbus:tcp:device:heatpump:energy-source#temperature-sensor-outside" }

Number                    Heatpump_CurrentCOP                                "Current COP"                             (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#cop" }
Number                    Heatpump_CurrentCOPHeating                         "Current COP Heating"                     (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#cop-heating" }
Number                    Heatpump_CurrentCOPdrinkingwater                   "Current COP drinking water"              (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#cop-drinkingwater" }
Number                    Heatpump_CurrentCOPCooling                         "Current COP Cooling"                     (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#cop-cooling" }
Number:Power              Heatpump_CurrentPower                              "Current Power"                           (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#power" }
Number:Power              Heatpump_Currentpowerheating                       "Current power heating"                   (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#power-heating" }
Number:Power              Heatpump_CurrentPowerDrinkingWater                 "Current Power Drinking Water"            (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#power-drinkingwater" }
Number:Power              Heatpump_Currentpowercooling                       "Current power cooling"                   (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#power-cooling" }
Number:Power              Heatpump_CurrentElectricPower                      "Current Electric Power"                  (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#electric-power" }
Number:Power              Heatpump_CurrentElectricPowerHeating               "Current Electric Power Heating"          (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#electric-power-heating" }
Number:Power              Heatpump_Currentelectricpowerdrinkingwater         "Current electric power drinking water"   (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#electric-power-drinkingwater" }
Number:Power              Heatpump_CurrentElectricPowerCooling               "Current Electric Power Cooling"          (kermi)         { channel="modbus:tcp:device:heatpump:power-channel#electric-power-cooling" }

Switch                    Heatpump_PVModulationActive                        "PV Modulation Active"                    (kermi)         { channel="modbus:tcp:device:heatpump:pv-modulation#pv-state" }
Number:Power              Heatpump_PVPower                                   "PV Power"                                (kermi)         { channel="modbus:tcp:device:heatpump:pv-modulation#pv-power" }
Number:Temperature        Heatpump_PVTempHeating                             "PV Temp Heating"                         (kermi)         { channel="modbus:tcp:device:heatpump:pv-modulation#pv-target-temperature-heating" }
Number:Temperature        Heatpump_PVTempDrinkingwater                       "PV Temp Drinkingwater"                   (kermi)         { channel="modbus:tcp:device:heatpump:pv-modulation#pv-target-temperature-drinkingwater" }

Number:Time               Heatpump_FanWorkhours                              "Fan Workhours"                           (kermi)         { channel="modbus:tcp:device:heatpump:workhours#workhours-fan" }
Number:Time               Heatpump_StorageLoadingPumpWorkhours               "StorageLoadingPump Workhours"            (kermi)         { channel="modbus:tcp:device:heatpump:workhours#workhours-storage-loading-pump" }
Number:Time               Heatpump_CompressorWorkhours                       "Compressor Workhours"                    (kermi)         { channel="modbus:tcp:device:heatpump:workhours#workhours-compressor" }

Persistence ​

You can / should persist some items you want to track, maybe you track your power consumption with another device (PV-System or 'smart' electricity meter), so you can compare these values.

Suggestion / Optional:
As these (power & temperature) values are long-running ones, maybe you should invest a little amount of time using influxDB as persistence (additionally to your existing default persistence in openHAB). InfluxDB is a good storage-solution for long terms and uses very small space for its data. Please read the documentation for better understanding how it works.

Visualization ​

As many other users I like and use the Grafana approach (in combination with influxdb). See here for more information InfluxDB & Grafana Tutorial

Credits ​

Credits goes to Bernd Weymann (Author of E3DC-Modbus-Binding). I used its basic structure / code and handling of Modbus Messages for this binding. Thanks.