HeliosVentilation Binding ​

This is the binding for Helios Ventilation Systems KWL EC 200/300/500 Pro. It requires a connection to the RS485 bus used by the original remote controls KWL-FB (9417), and does not use the Modbus/TCP interface of the newer EasyControl devices.

For electrical connection it is recommended to use an USB-RS485 interface, but any RS485 interface that shows up as a serial port will do. Setup the device as described in </docs/administration/serial.html>.

The binding will use the remote control address 15 for communication, so make sure that this is not assigned to a physically present remote control.

For Helios ventilation devices supporting the easyControls web interface, the separate Helios easyControls binding can be used.

Supported Things ​

There is only one Thing type supported by this binding: a Helios Ventilation System KWL EC 200/300/500 Pro from Helios. The binding was developed and tested on a KWL EC 200 Pro device.

Binding Configuration ​

The binding requires access to the serial device connecting to the RS485 bus as described in </docs/administration/serial.html>. Otherwise only Thing configuration is needed.

Thing Configuration ​

The binding supports only one Thing and requires the configuration of the serial port (typically /dev/ttyUSB0 on Linux and COM3 on Windows) and optionally the polling time which is the cycle time after which the binding tries to reconnect to the bus and requests data updates.

Channels ​

Supported operation channels:

channeltypedescription
outsideTempNumber:TemperatureTemperature sensor in the outside air flow
outgoingTempNumber:TemperatureTemperature sensor in the outgoing air flow
extractTempNumber:TemperatureTemperature sensor in the extract air flow
supplyTempNumber:TemperatureTemperature sensor in the supply air flow
setTempNumber:TemperatureSet temperature for supply (not always used)
fanspeedNumberLevel of the fanspeed (1-8)
powerStateSwitchMain power switch
co2StateSwitchSwitch for CO2 regulation
rhStateSwitchSwitch for humidity regulation
winterModeSwitchSwitch to set winter mode

Supported configuration channels:

channeltypedescription
bypassTempNumber:TemperatureTemperature to disable the bypass function
supplyStopTempNumber:TemperatureTemperature to stop the supply fan for defrost
preheatTempNumber:TemperatureTemperature to enable the preheater
minFanspeedNumberMinimal level of the fanspeed (1-8)
maxFanspeedNumberMaximal level of the fanspeed (1-8)
rhLimitNumber:DimensionlessLimit for relative humidity sensor
hysteresisNumber:TemperatureHysteresis on defroster temperature
DCFanExtractNumber:DimensionlessSpeed reduction for the extract fan
DCFanSupplyNumber:DimensionlessSpeed reduction for the supply fan
maintenanceIntervalNumber:DimensionlessMaintenance interval in months
adjustIntervalNumber:DimensionlessAdjust interval in minutes for air quality
RHLevelAutoSwitchAutomatic base humidity determination
switchTypeSwitchExternal switch type (Boost or Fireplace)
radiatorTypeSwitchUse water (ON) or electric (OFF) radiator
cascadeSwitchSystem is cascaded

Note: the configuration channels are not intended to be written regularly.

Full Example ​

heliosventilation.things:

java
heliosventilation:ventilation:MyKWL  [ serialPort="/dev/ttyUSB0" ]

heliosventilation.items:

dsl
Switch KWLOnOff { channel="heliosventilation:ventilation:MyKWL:powerState" }
Switch KWLWinter { channel="heliosventilation:ventilation:MyKWL:winterMode" }

Group VentilationTemp "Measured Temperatures in Ventilation System"

Number:Temperature Outside_Temperature "Outside Temperature [%.1f °C]" <temperature> (VentilationTemp) { channel="heliosventilation:ventilation:MyKWL:outsideTemp" }
Number:Temperature Outgoing_Temperature "Outgoing Temperature [%.1f °C]" <temperature> (VentilationTemp) { channel="heliosventilation:ventilation:MyKWL:outgoingTemp" }
Number:Temperature Extract_Temperature "Extract Temperature [%.1f °C]" <temperature> (VentilationTemp) { channel="heliosventilation:ventilation:MyKWL:extractTemp" }
Number:Temperature Supply_Temperature "Supply Temperature [%.1f °C]" <temperature> (VentilationTemp) { channel="heliosventilation:ventilation:MyKWL:supplyTemp" }

Number Fan_Speed "Fan Speed" <fan> { channel="heliosventilation:ventilation:MyKWL:fanspeed" }
Number Min_Fan_Speed "Min Fan Speed" <fan> { channel="heliosventilation:ventilation:MyKWL:minFanspeed" }
Number Max_Fan_Speed "Max Fan Speed" <fan> { channel="heliosventilation:ventilation:MyKWL:maxFanspeed" }

heliosventilation.sitemap:

dsl
sitemap helios_kwl label="Helios Ventilation" {
        Frame label="Temperatures" {
              Text item=Outside_Temperature
              Text item=Outgoing_Temperature
              Text item=Extract_Temperature
              Text item=Supply_Temperature
        }
        Frame label="Control" {
              Switch item=KWLOnOff
              Switch item=KWLWinter
              Slider item=Fan_Speed icon="fan" minValue=1 maxValue=8 step=1
        }
        Frame label="Configuration" {
              Slider item=Min_Fan_Speed
              Setpoint item=Max_Fan_Speed icon="fan"
        }
}